Its
compact design and combination of set-point sensitivity and narrow or optional
adjustable deadband, offers cost-saving solutions for a variety of
applications. The J6 is ideally suited for a wide range of industrial processes
such as alarm/shutdown and low/high service pressures. OEMs also utilize the J6
in machinery and equipment for threshold protection.
Specifications for
Interruptores de presión de la serie J6 de UE Controls, modelos 126-160
Pressure parameters .
126 -Set Point Range: 30 ”Hg Vac to 0 psi /Deadband: 0.2 to 0.8 ”Hg /Over Range Pressure: 3 psi / Proof pressure: 5 psi
or
134 -Set Point Range: 30 ”Hg Vac to 20 psi /Deadband: 0.2 to 0.8 ”Hg /Over Range Pressure: 20 psi / Proof pressure: 25 psi
or
136 -Set Point Range: 0 to 50” wc /Deadband: 3 to 6 ”wc /Over Range Pressure: 50 “wc / Proof pressure: 5 psi
or
142 -Set Point Range: 0 to 18 psi /Deadband: 4 to 7 ”wc /Over Range Pressure: 18 psi / Proof pressure: 25 psi
or
148 -Set Point Range: 0 to 40 psi /Deadband: 0.1 to 0.4 psi /Over Range Pressure: 40 psi / Proof pressure: 40 psi
or
152 -Set Point Range: 0 to 50 psi /Deadband: 0.1 to 0.5 psi /Over Range Pressure: 50 psi / Proof pressure: 75 psi
or
156 -Set Point Range: 3 to 100 psi /Deadband: 0.2 to 0.8 psi /Over Range Pressure: 100 psi / Proof pressure: 75 psi
or
160 -Set Point Range: 50 to 180 psi /Deadband: 0.3 to 1 psi /Over Range Pressure: 180 psi / Proof pressure: 180 psi