One Series Safety Transmitter Overview
The One Series Safety Transmitter is a transmitter-switch for monitoring
pressure or temperature and meets the requirements of SIL 2 for random
integrity at HFT = 0, SIL 3 for random integrity at HFT = 1 and SIL 3 for
systematic capability. The One Series Safety Transmitter incorporates UE’s
patented IAW self diagnostics, redundant and diverse signal processing and
software algorithms to detect abnormalities in the process and internal faults.
The design is based on a powerful microprocessor that provides an extremely
fast response time for emergency shutdown situations.
Sensors
- – 316L stainless steel, welded diaphragm, 1/2” NPT (female) process connection, micro-machined piezo-resistive strain gauge silicon element, 0.25 ml silicone oil fill. Maximum media temperature: -40 to 257°F (-40 to 125°C).
- - 316L stainless steel, welded diaphragms, 1/4” NPT (male) process connections, piezoresistive strain gauge silicon element, silicone oil fill. Maximum media temperature: -40 to 257°F (-40 to 125°C).
- – 316 stainless steel 0.25” OD sheath containing a 100 ohm 4-wire platinum RTD element available with epoxy fill (local low temp) or powder fill (remote high temp). Media temperature limits: -328 to 1000°F, intermittent to 1100°F (-200 to 538°C, int. to 593°C) for TH and TT ranges -40 to 500°F (-40 to 260°C) for TR and TL ranges.
Gauge Pressure
Differential Pressure
Temperature
Applications
Measuring gauge pressure, differential pressure or temperature.
For plant upgrades and new construction projects.
Specifications
Power input/Switch output:
Voltage and Current Maximum Ratings
S ignal Name |
2SLP47 |
2SLP48 |
2SLP49 |
Power Supply |
2-wire 20-40 VDC @ 4-20 mA (Loop or Fixed Current) |
2-wire 20-40 VDC @ 4-20 mA (Loop or Fixed Current) |
2-wire 20-40 VDC @ 4-20 mA (Loop or Fixed Current) |
Safety Relay Output |
12-250 VAC @ 5 mA-5 A |
0-30 VDC @ 6 A, 1.8 A Pilot Duty |
0-130 VDC @ 2.5 A, Q1501 Pilot Duty |
With Relay Monitor Enabled |
12-250 VAC @ 5 mA-5 A |
10-30 VDC @ 5 mA-6 A |
10-130 VDC @ 5 mA-2.5 A |
Temperature Derating |
1% per ˚ C above 25˚C |
1% per ˚ C above 25˚C |
1% per ˚ C above 25˚C |
SRO Status |
30 VDC @ 20 mA |
30 VDC @ 20 mA |
30 VDC @ 20 mA |
IAW Output |
30 VDC @ 20 mA |
30 VDC @ 20 mA |
30 VDC @ 20 mA |
Accuracy:
0.5% of full range span, at room temperature
Repeatability:
0.1% of full range span
Status Outputs:
SRO Status - 30 VDC @ 20 mA Maximum/ IAW Output - 30 VDC @ 20 mA Maximum
Switch response time:
“Change-of-output” response ≤ 100 mS (for detection of full step change and change of output state, Filter feature off) Enclosure: Type 4X/IP66 certified polyester painted aluminum alloy 360, vented for ranges P08-P14
Display:
Backlit/ Local 4 digit x 0.5” LCD/ IAW® (I Am Working) status/ Process variable Units of measure/ Switch status/ Latch status/ Set point value/ Deadband value/ Min/Max values/ Fault codes
Memory:
Programming and data protected by non-volatile EEPROM
Emission:
EN 61000-6-4 Class A
EMI/RFI:
Compliance to CE EMC requirements: EN 61000-6-2, EN 61000-6-4
Memory: Programming and data protected by non-volatile EEPROM
Dimensional Drawings
Enclosure and sensor details
Approvals
N. America [vii]
TCD50
- Class I Div. 1, Groups C & D, T4
- United States
- Class I, Zone 1, AEx db ia [ia] IIB T4 Gb
- Enclosure Type 4X, IP66[v]
- Canada
- Class I, Zone 1, Ex db ia [ia] IIB T4 Gb
- -40 °C < Ta < +65 °C [vi]
TCD60
- ITS-121ATEX31360X
- II 2 (2) G Ex db ia [ia] IIC T4 Gb
- IP66 [v]
- -40 °C < Tamb < +65 °C [vi]
Europe [vii]
TCD50
- ITS 16 ATEX 18474
- II 2 (2) G Ex db ia [ia] IIB T4 Gb
- IP66 [v]
- -40 °C < Tamb < +65 °C [vi]
TCD60
- ITS-121ATEX31360X
- II 2 (2) G Ex db ia [ia] IIC T4 Gb
- IP66 [v]
- -40 °C < Tamb < +65 °C [vi]
International [vii]
TCD50
- IECEx ETL 16.0016
- Ex db ia [ia] IIB T4 Gb
- IP66 [v]
- -40°C < Tamb < +65 °C [vi]
TCD60
- IECEx ETL 21.0065X
- Ex db ia [ia] IIC T4 Gb
- IP66 [v]
- -40 °C < Tamb < +65 °C [vi]